VENUS E Mini troubleshooting and alarm codes

This page reproduces section 4.2 of the MARSTEK Venus E Mini user manual (MST-BIE2-1500). A fault shows as a red Warn/Error LED on the front panel. Check the code in the MARSTEK app.

Users must not open the unit

The manual says the Venus E Mini "should only be repaired by authorized personnel. Users are strictly prohibited from disassembling or repairing any internal components." Unplug it from the socket before any maintenance. In the table below, "turn the inverter off / power off the unit" means switching the Mini off with its On/Off button, nothing more.

General procedure​

  1. Check all electrical connections and the battery status.
  2. Restart the system using the proper power-cycling procedure.
  3. Look up known issues in the user manual or FAQ.
  4. If the problem continues, contact customer support with: full device specifications, a detailed description of the fault, and any error codes or indicator states.

Alarm-code table​

"Restart (5 min)" below is short for the manual's: "Turn the inverter off, wait for 5 minutes, and restart. If the problem persists, contact the manufacturer for technical support."

CodeAlarmPossible causeSuggestions
1Bus Overvoltage1. Abnormal fluctuation in grid voltage. 2. Internal inverter failure.1. Turn the inverter off and check the grid voltage for abnormalities. 2. If no issues are found, wait 5 minutes and restart. 3. If it persists, contact the manufacturer.
2Bus Undervoltage1. Not enough energy from the battery while running off-grid. 2. Internal inverter failure.1. Check the battery level. 2. If energy is low, connect to the grid and check it runs normally. 3. If it persists, contact the manufacturer.
3Bus Unbalance1. Connected load is very unbalanced. 2. Internal inverter failure.1. Remove all loads and check whether the system returns to normal. 2. Restart (5 min). 3. If it persists, contact the manufacturer.
4Relay FaultInternal inverter failure.Restart (5 min).
5Communication FaultInternal inverter failure.Restart (5 min).
6Storage FaultInternal inverter failure.Restart (5 min).
7Sampling ErrorInternal inverter failure.Restart (5 min).
8Grid Overfrequency1. Abnormal local grid frequency. 2. Internal inverter failure.Restart (5 min).
9Grid Underfrequency1. Abnormal local grid frequency. 2. Internal inverter failure.Restart (5 min).
10Grid Overvoltage1. Abnormal local grid frequency (as printed; probably meant "voltage"). 2. Internal inverter failure.Restart (5 min).
11Grid Undervoltage1. Abnormal local grid voltage. 2. Grid is not connected. 3. Internal inverter failure.1. Wait for the grid voltage to return to normal. 2. Check that the grid is properly connected. 3. If it does not recover for a long time, contact the manufacturer.
12Grid Loss1. Local grid failure. 2. Internal inverter failure.1. Power off the unit and check whether the local grid voltage is normal. 2. Wait 5 minutes and restart. 3. If it persists, contact the manufacturer.
13Inverter Overcurrent1. Short circuit at the LOAD terminals. 2. Abnormal local grid. 3. Internal inverter failure.1. Power off the unit and check the output terminals for a short circuit. 2. Wait 5 minutes and restart.
14Abnormal Frequency1. Abnormal local grid frequency. 2. Internal inverter failure.1. Wait for the grid frequency to return to normal. 2. Power off, wait 5 minutes and restart. 3. If it doesn't return to normal, contact the manufacturer.
15Inverter Overvoltage1. Abnormal local grid voltage. 2. Internal inverter failure.1. Power off, wait 5 minutes and restart. 2. If it persists, contact the manufacturer.
16Inverter UndervoltageInternal inverter failure.1. Power off, wait 5 minutes and restart. 2. If it persists, contact the manufacturer.
17Inverter Soft Start FailureInternal inverter failure.1. Power off, wait 5 minutes and restart. 2. If it persists, contact the manufacturer.
18Bus Soft Start FailureInternal inverter failure.Power off / restart (5 min).
19Inverter Overtemperature1. Heat sink is blocked. 2. Ambient temperature too high. 3. Internal inverter failure.1. Turn the inverter off, check whether the heat sink is blocked, and let it cool down before restarting. 2. If it persists, contact the manufacturer.
20DC Resonant Cavity Overcurrent (Comparator)1. Abnormal local grid voltage. 2. Internal inverter failure.Restart (5 min).
21DC High-Voltage Bus Overvoltage (Comparator)Internal inverter failure.Restart (5 min).
22Inverter Short Circuit1. Short circuit at the output terminals. 2. Internal inverter failure.1. Power off the unit and check the output terminals for a short circuit. 2. Wait 5 minutes and restart. 3. If it persists, contact the manufacturer.
23Abnormal Leakage Current1. Not enough insulation between PV panels and ground. 2. Internal inverter failure.1. Check all wiring for damage and verify insulation to ground. 2. Restart (5 min). 3. If it persists, contact the manufacturer.
24Meter Communication Fault1. Meter connection is abnormal. 2. Internal inverter failure.1. Power off the unit and check the meter connection. 2. If it persists, contact the manufacturer.
25Overtemperature Derating1. Heat sink is blocked. 2. Ambient temperature too high. 3. Internal inverter failure.1. Turn the inverter off, check the heat sink and let it cool before restarting. 2. If it persists, contact the manufacturer.
26Balancing Bridge Arm OvercurrentInternal inverter failure.Restart (5 min).
27Inverter Hardware Overcurrent1. Short circuit at the output terminals. 2. Grid terminal struck by lightning. 3. Internal inverter failure.1. Power off the unit and check the output terminals for a short circuit. 2. Wait 5 minutes and restart. 3. If it persists, contact the manufacturer.
28Off-grid Overload1. Load power is above the rated power. 2. Connected load has a high inrush current.1. Check whether the total load is too high. 2. If it persists, contact the manufacturer.
29Battery Overvoltage1. Battery overcharged. 2. Poor cell consistency (one cell voltage too high). 3. Internal battery pack failure.Power off the unit and contact the manufacturer for technical support.
30Battery Undervoltage1. Battery self-discharged after long storage. 2. Internal battery pack failure.1. Connect the grid to use the battery activation function for charging. 2. If the battery cannot be activated, contact the manufacturer.
31Battery Overcurrent1. Battery output power above the rated power. 2. Internal battery pack failure.1. Turn the inverter off, wait 5 minutes, connect to the grid and restart. 2. If it persists, contact the manufacturer.
32Battery Overtemperature1. Heat sink is blocked. 2. Ambient temperature too high. 3. Internal battery pack failure.1. Turn the inverter off, check the heat sink, and let the battery cool before restarting. 2. If it persists, contact the manufacturer.
33Battery Low Temperature1. Ambient temperature too low. 2. Internal battery pack failure.1. Turn the inverter off and check that the ambient temperature is within the normal operating range. 2. If it persists, contact the manufacturer.
34Battery ShortInternal battery pack failure.Power off the unit and contact the manufacturer for technical support.
35Battery Overload1. Battery output power above the rated power. 2. Internal battery pack failure.1. Turn the inverter off, wait 5 minutes, connect to the grid and restart. 2. If it persists, contact the manufacturer.
36Low Battery State of Health (SOH)Battery cell performance has degraded.Contact the manufacturer for technical support.
37Battery Full Charge ProtectionBattery is fully charged.Stop charging the battery.
How this table was reconstructed

The Drive text extraction of the Mini manual breaks the table layout. On pages 13–15 the suggestions are separated from their codes. Codes 1–7, 13–17 and 28–37 come through cleanly. For codes 8–12 and 18–27, this page matches each suggestion to its code by content (e.g. the "check the meter connection" suggestion goes to code 24, Meter Communication Fault). Codes 18, 20, 21 and 26 all use the same "power off, wait 5 minutes, restart" advice, so the exact pairing does not change what to do. Check against the PDF before quoting a code as definitive.

Code 23 mentions PV panels

Code 23's cause says "insulation between PV panels and ground". The Mini is an AC-coupled battery with no PV input in its spec table, so this text looks inherited from MARSTEK's hybrid-inverter manuals. If code 23 appears, check the Mini's AC wiring and earthing, and escalate to MARSTEK support.