V6000 troubleshooting and alarm codes
When the V6000 has a fault, the fault indicator on the front display lights up and shows a three-digit fault code (manual section 5.2). This page reproduces the Alarm Code Index from the appendix of the V6000 user manual V1.0.
The manual says: "Deep maintenance, annual servicing, or any operations that involve opening the equipment enclosure or accessing internal high-voltage components must NOT be performed by the user... must only be carried out by our certified professional technicians." The steps below are limited to restarting, removing loads, checking inputs and the environment, and contacting support. Before any wiring check, the unit must be fully de-energised.
Quick guide to the suggested actions
| Action in the table | What it means |
|---|---|
| Restart | Restart the unit and check whether the fault clears. If it persists, contact the manufacturer for technical support. |
| Remove loads | Remove all loads and restart the unit. Optionally reconnect with a smaller load. Check whether the fault clears. If it persists, contact the manufacturer. |
| Stop & call | Power off the unit and contact the manufacturer for technical support immediately. |
| Check PV | Power off the unit and check whether the PV input is normal, then restart. If it persists, contact the manufacturer. |
| Cool down | Power off the unit and check the ambient temperature. Place it somewhere between 0 °C and 50 °C, let it rest for 10 minutes, then restart. If the fault does not clear, contact the manufacturer. |
Inverter / power-stage codes (001–041)
| Code | Alarm | Suggestion |
|---|---|---|
| 001 | BUS Overvoltage | Restart |
| 002 | BUS Undervoltage | Restart |
| 003 | BUS Soft-Start Timeout | Restart |
| 004 | Inverter Soft-Start Timeout | Restart |
| 005 | Inverter Overcurrent (Software) | Remove loads |
| 006 | Inverter Overcurrent (Hardware) | Remove loads |
| 007 | Inverter Undervoltage | Restart |
| 008 | Inverter Overvoltage | Restart |
| 009 | Inverter Output Short Circuit | Remove loads |
| 010 | Inverter Circuit Sensor Fault | Restart |
| 011 | Unexpected Current Feedback Into Inverter | Stop & call |
| 012 | Overload | Remove loads |
| 013 | Output Current Sensor Fault | Restart |
| 014 | Current Sharing Sensor Fault | Restart |
| 015 | Input/Output Reverse Connection | Stop & call |
| 016 | Output Relay Fault | Stop & call |
| 017 | Battery Overvoltage | Discharge the unit. If the problem persists, contact the manufacturer. |
| 018 | Buck-Boost Overcurrent | Restart |
| 019 | Buck-Boost Current Sensor Fault | Restart |
| 020 | Buck-Boost Filter Current Sensor Fault | Restart |
| 021 | DC/DC Soft-Start Failure | Restart |
| 022 | Buck-Boost Hardware Overcurrent | Remove loads |
| 023 | LLC Overcurrent | Remove loads |
| 024 | LLC Transformer Fault | Stop & call |
| 025 | PV Overvoltage | Check PV |
| 026 | PV Short Circuit | Check PV |
| 027 | PV Power Abnormality | Check PV |
| 028 | PV Input Overcurrent | Check PV |
| 029 | Fan Locked Rotor | Stop & call |
| 030 | PV Side Overtemperature / NTC Disconnected | Cool down |
| 031 | Inverter Side Overtemperature / NTC Disconnected | Cool down |
| 032 | LLC Low-Voltage Side Overtemperature / NTC Disconnected | Cool down |
| 033 | LLC High-Voltage Side Overtemperature / NTC Disconnected | Cool down |
| 034 | LLC Transformer Overtemperature | Cool down |
| 035 | Parallel CAN Communication Fault | Check the parallel wiring connections. If it persists, contact the manufacturer. |
| 036 | Parallel Master Signal Loss | Check the parallel wiring connections. If it persists, contact the manufacturer. |
| 037 | Parallel Sync Signal Loss | Check the parallel wiring connections. If it persists, contact the manufacturer. |
| 038 | Parallel Version Mismatch | Try upgrading the software to the latest version and check whether the fault clears. If it persists, contact the manufacturer. |
| 039 | Parallel Output Current Fault | Restart |
| 040 | Parallel Output Configuration Error | Check the parallel operation configuration settings. |
| 041 | Incorrect Standalone Wiring Used in Parallel Mode | Check that the parallel wiring and configuration settings match. |
Battery / BMS codes (101–115)
| Code | Alarm | Suggestion |
|---|---|---|
| 101 | Module Overvoltage | Power off and wait 5 minutes. Power on and check whether the fault clears. If it persists, contact the manufacturer. |
| 102 | Module Undervoltage | Connect the unit to the grid or PV to charge the battery and check whether it resolves. If not, contact the manufacturer. |
| 103 | Cell Overvoltage | Power off and wait 5 minutes, then check whether the fault clears. If it persists, contact the manufacturer. |
| 104 | Cell Undervoltage | Connect the unit to the grid or a charger to charge the battery and check whether it resolves. If not, contact the manufacturer. |
| 105 | Cell Overtemperature | Power off and wait, then check whether the fault clears. If it persists, contact the manufacturer. |
| 106 | Cell Undertemperature | Check the ambient temperature, restart and check whether the fault clears. If it persists, contact the manufacturer. |
| 107 | MOSFET Overtemperature | Check the ambient temperature, restart and check whether the fault clears. If it persists, contact the manufacturer. |
| 108 | Charge Overcurrent | Disconnect the grid and PV supply, then restart and check whether the fault clears. If it persists, contact the manufacturer. |
| 109 | Discharge Overcurrent | Remove loads |
| 110 | System Fault Protection | Restart |
| 111 | Charge MOSFET Failure | Stop & call |
| 112 | Discharge MOSFET Failure | Stop & call |
| 113 | Ambient Overtemperature Protection | Check the ambient temperature and keep the device between 0–50 °C. If it does not resolve, contact the manufacturer. |
| 114 | Ambient Undertemperature Protection | Check the ambient temperature and keep the device between 0–50 °C. If it does not resolve, contact the manufacturer. |
| 115 | Short Circuit Protection | Restart |
Communication / upgrade codes (201–205)
| Code | Alarm | Suggestion |
|---|---|---|
| 201 | MQTT Session Connection Failed: Socket Connection Failure | Restart |
| 202 | MQTT Session Connection Failed: Client Identifier Occupied | Restart |
| 203 | MQTT Client-Server Connection Failed | Restart |
| 204 | INV: No Response to Prepare Upgrade Command | Restart |
| 205 | BMS: No Response to Prepare Upgrade Command | Restart |
The Drive text extraction lists some alarm names apart from their code numbers (011–016, 023–028, 033–037, 103–108 and 201–205). This page pairs them in the order they appear, checked against each suggestion (for example, the "check the ambient temperature" steps go with the temperature alarms). All five 201–205 codes share the same "restart" advice, so their exact order does not change what to do. Check the PDF before quoting a specific code as definitive.
Common situations
These are explanations based on the table, not extra manual instructions.
| Situation | Likely codes | First step |
|---|---|---|
| Too many appliances on AC-OUT, or a motor or compressor with high start-up current | 005, 006, 009, 012, 109 | Remove loads, restart, then add loads back gradually. AC output is 6 kW continuous / 12 kW peak. |
| Unit in a hot room or direct sun | 030–034, 105, 107, 113 | Move it or ventilate the space to keep it between 0–50 °C, rest 10 minutes, then restart. |
| Solar problem after rain or new panel work | 025–028 | Power off and have the installer check the PV strings (80–500 V, 16 A max per input). |
| Battery flat after a long brownout | 102, 104 | Reconnect the grid or PV to recharge. |
| App or cloud not updating | 201–205 | Restart the unit and check the Wi-Fi. |
When to stop using it and call for service
From manual section 7.2, stop using the V6000 immediately and contact Silvera Solar Power or MARSTEK if you see:
- persistent alarm codes on the display;
- unusual noise, smell, or visible overheating, bulging or leakage;
- a sudden, unexplained drop in capacity or output power;
- any cable, terminal or connector that looks burnt or discoloured, or can't be tightened securely.
Emergencies (manual section 1.5)
- Electrolyte leak: don't enter the room, and avoid the liquid and gas. Call emergency services if needed. For eye or skin contact, rinse with plenty of water for at least 15 minutes and get medical help.
- Fire: switch off all connected power sources if safe. For a battery fire, use fire sand, a CO2 extinguisher or other approved electrical-fire equipment. If the fire hasn't reached the battery, a Type ABC extinguisher can be used. Watch for re-ignition.
- Flood: don't touch the unit and switch off all breakers. Wait for the water to recede, then contact MARSTEK or an authorised service partner. Do not reuse a flooded battery.
Related pages
Sources
- V6000 user manual V1.0 (Drive): Appendix Alarm Code Index, sections 1.5, 5.2, 7.2