V6000 troubleshooting and alarm codes

When the V6000 has a fault, the fault indicator on the front display lights up and shows a three-digit fault code (manual section 5.2). This page reproduces the Alarm Code Index from the appendix of the V6000 user manual V1.0.

Do not open the enclosure

The manual says: "Deep maintenance, annual servicing, or any operations that involve opening the equipment enclosure or accessing internal high-voltage components must NOT be performed by the user... must only be carried out by our certified professional technicians." The steps below are limited to restarting, removing loads, checking inputs and the environment, and contacting support. Before any wiring check, the unit must be fully de-energised.

Quick guide to the suggested actions​

Action in the tableWhat it means
RestartRestart the unit and check whether the fault clears. If it persists, contact the manufacturer for technical support.
Remove loadsRemove all loads and restart the unit. Optionally reconnect with a smaller load. Check whether the fault clears. If it persists, contact the manufacturer.
Stop & callPower off the unit and contact the manufacturer for technical support immediately.
Check PVPower off the unit and check whether the PV input is normal, then restart. If it persists, contact the manufacturer.
Cool downPower off the unit and check the ambient temperature. Place it somewhere between 0 °C and 50 °C, let it rest for 10 minutes, then restart. If the fault does not clear, contact the manufacturer.

Inverter / power-stage codes (001–041)​

CodeAlarmSuggestion
001BUS OvervoltageRestart
002BUS UndervoltageRestart
003BUS Soft-Start TimeoutRestart
004Inverter Soft-Start TimeoutRestart
005Inverter Overcurrent (Software)Remove loads
006Inverter Overcurrent (Hardware)Remove loads
007Inverter UndervoltageRestart
008Inverter OvervoltageRestart
009Inverter Output Short CircuitRemove loads
010Inverter Circuit Sensor FaultRestart
011Unexpected Current Feedback Into InverterStop & call
012OverloadRemove loads
013Output Current Sensor FaultRestart
014Current Sharing Sensor FaultRestart
015Input/Output Reverse ConnectionStop & call
016Output Relay FaultStop & call
017Battery OvervoltageDischarge the unit. If the problem persists, contact the manufacturer.
018Buck-Boost OvercurrentRestart
019Buck-Boost Current Sensor FaultRestart
020Buck-Boost Filter Current Sensor FaultRestart
021DC/DC Soft-Start FailureRestart
022Buck-Boost Hardware OvercurrentRemove loads
023LLC OvercurrentRemove loads
024LLC Transformer FaultStop & call
025PV OvervoltageCheck PV
026PV Short CircuitCheck PV
027PV Power AbnormalityCheck PV
028PV Input OvercurrentCheck PV
029Fan Locked RotorStop & call
030PV Side Overtemperature / NTC DisconnectedCool down
031Inverter Side Overtemperature / NTC DisconnectedCool down
032LLC Low-Voltage Side Overtemperature / NTC DisconnectedCool down
033LLC High-Voltage Side Overtemperature / NTC DisconnectedCool down
034LLC Transformer OvertemperatureCool down
035Parallel CAN Communication FaultCheck the parallel wiring connections. If it persists, contact the manufacturer.
036Parallel Master Signal LossCheck the parallel wiring connections. If it persists, contact the manufacturer.
037Parallel Sync Signal LossCheck the parallel wiring connections. If it persists, contact the manufacturer.
038Parallel Version MismatchTry upgrading the software to the latest version and check whether the fault clears. If it persists, contact the manufacturer.
039Parallel Output Current FaultRestart
040Parallel Output Configuration ErrorCheck the parallel operation configuration settings.
041Incorrect Standalone Wiring Used in Parallel ModeCheck that the parallel wiring and configuration settings match.

Battery / BMS codes (101–115)​

CodeAlarmSuggestion
101Module OvervoltagePower off and wait 5 minutes. Power on and check whether the fault clears. If it persists, contact the manufacturer.
102Module UndervoltageConnect the unit to the grid or PV to charge the battery and check whether it resolves. If not, contact the manufacturer.
103Cell OvervoltagePower off and wait 5 minutes, then check whether the fault clears. If it persists, contact the manufacturer.
104Cell UndervoltageConnect the unit to the grid or a charger to charge the battery and check whether it resolves. If not, contact the manufacturer.
105Cell OvertemperaturePower off and wait, then check whether the fault clears. If it persists, contact the manufacturer.
106Cell UndertemperatureCheck the ambient temperature, restart and check whether the fault clears. If it persists, contact the manufacturer.
107MOSFET OvertemperatureCheck the ambient temperature, restart and check whether the fault clears. If it persists, contact the manufacturer.
108Charge OvercurrentDisconnect the grid and PV supply, then restart and check whether the fault clears. If it persists, contact the manufacturer.
109Discharge OvercurrentRemove loads
110System Fault ProtectionRestart
111Charge MOSFET FailureStop & call
112Discharge MOSFET FailureStop & call
113Ambient Overtemperature ProtectionCheck the ambient temperature and keep the device between 0–50 °C. If it does not resolve, contact the manufacturer.
114Ambient Undertemperature ProtectionCheck the ambient temperature and keep the device between 0–50 °C. If it does not resolve, contact the manufacturer.
115Short Circuit ProtectionRestart

Communication / upgrade codes (201–205)​

CodeAlarmSuggestion
201MQTT Session Connection Failed: Socket Connection FailureRestart
202MQTT Session Connection Failed: Client Identifier OccupiedRestart
203MQTT Client-Server Connection FailedRestart
204INV: No Response to Prepare Upgrade CommandRestart
205BMS: No Response to Prepare Upgrade CommandRestart
How this table was reconstructed

The Drive text extraction lists some alarm names apart from their code numbers (011–016, 023–028, 033–037, 103–108 and 201–205). This page pairs them in the order they appear, checked against each suggestion (for example, the "check the ambient temperature" steps go with the temperature alarms). All five 201–205 codes share the same "restart" advice, so their exact order does not change what to do. Check the PDF before quoting a specific code as definitive.

Common situations​

These are explanations based on the table, not extra manual instructions.

SituationLikely codesFirst step
Too many appliances on AC-OUT, or a motor or compressor with high start-up current005, 006, 009, 012, 109Remove loads, restart, then add loads back gradually. AC output is 6 kW continuous / 12 kW peak.
Unit in a hot room or direct sun030–034, 105, 107, 113Move it or ventilate the space to keep it between 0–50 °C, rest 10 minutes, then restart.
Solar problem after rain or new panel work025–028Power off and have the installer check the PV strings (80–500 V, 16 A max per input).
Battery flat after a long brownout102, 104Reconnect the grid or PV to recharge.
App or cloud not updating201–205Restart the unit and check the Wi-Fi.

When to stop using it and call for service​

From manual section 7.2, stop using the V6000 immediately and contact Silvera Solar Power or MARSTEK if you see:

  • persistent alarm codes on the display;
  • unusual noise, smell, or visible overheating, bulging or leakage;
  • a sudden, unexplained drop in capacity or output power;
  • any cable, terminal or connector that looks burnt or discoloured, or can't be tightened securely.

Emergencies (manual section 1.5)​

  • Electrolyte leak: don't enter the room, and avoid the liquid and gas. Call emergency services if needed. For eye or skin contact, rinse with plenty of water for at least 15 minutes and get medical help.
  • Fire: switch off all connected power sources if safe. For a battery fire, use fire sand, a CO2 extinguisher or other approved electrical-fire equipment. If the fire hasn't reached the battery, a Type ABC extinguisher can be used. Watch for re-ignition.
  • Flood: don't touch the unit and switch off all breakers. Wait for the water to recede, then contact MARSTEK or an authorised service partner. Do not reuse a flooded battery.